TZY-MMI-A Low Voltage Motor Control and Protection Device
Add time:2022-02-21
Page views:102
Dial +86-312-3156390 / 3155390The TZY-MMI-A series low-voltage motor control and protection device is suitable for 380V~660V low-voltage systems. As a new generation of intelligent protection and measurement device for the protection, monitoring, and control of low-voltage motor feeder terminals, it protects the motor from starting thermal overload, locked rotor, phase loss, reverse phase, current imbalance, zero sequence overcurrent, leakage overcurrent, low voltage, overvoltage, voltage recovery self starting, undercurrent, tE time protection, and process interlocking that occur during starting and operation. At the same time, it provides fault tripping records, which brings great convenience to accident analysis. The use of its bus communication function enables data exchange with servers or workstations, making it an ideal choice for intelligent MMI and factory DCS system intelligent terminal units.
The TZY-MMI-A series low-voltage control and protection device can be widely used in various industries such as power, metallurgy, petrochemicals, textiles, papermaking, municipal engineering, etc.
1. Adopting a 32-bit high-performance industrial grade low-power microprocessor.
2. The 'tE time protection' complies with the regulations for overload protection of increased safety explosion-proof motors (GB3836.3-2000) and is suitable for protecting increased safety explosion-proof motors in continuous operation.
3. The device automatically calculates zero sequence current without the need for an external zero sequence current transformer.
4. By using AC sampling technology, parameters such as three-phase current, leakage current, voltage, active power, reactive power, and power factor of the motor can be measured, displayed, and transmitted.
5. The analog input, switch input, and switch output modules all use complete electrical isolation technology.
6. 6 analog inputs, Ia、Ib、Ic、IL、Uab、Ucb.
7. 10 switch inputs, including 6 fixed inputs and 4 programmable inputs, can achieve rich interlocking functions and facilitate engineering design.
8. 7 switch outputs, including 3 programmable outputs and 4 fixed outputs.
9. Time display.
10. 2-channel 4-20mA intelligent analog output, which can select any one of Ia, Ib, Ic, IL, Uab, Ucb according to user needs.
11. The protection function can achieve remote switching, and the alarm signal can achieve remote reset.
12. Two standard communication buses and protocols such as RS485/MODBUS/PROFIBUS can be used for actual dual network communication.
13. You can search for 10 more recent tripping accident records.
14. Electromagnetic compatibility meets the electrical standard IEC IV level.
4.1 Analog input circuit of TZY-MMI-A series
Rated current: In~150A
Rated frequency: Fn 0Hz
Power consumption: CT circuit ≤ 1W per phase
Overload capacity: CT circuit in continuous operation
10In,10S
40In,2S
Overload capacity: PT circuit 1.2Un continuous operation
1.4Un,10S
Measurement accuracy: Current level 0.5
Voltage level 0.5
Power level 0.5
Electricity level 1
4.2 Switching input
| Quantity | 10‑channel |
| Built‑in Supply Voltage | 24VDC |
| Max. External Resistance | 1000Ω |
| Input Conversion Response Time | <50ms |
4.3 Relay output
| X2.1‑X2.2(Device Power‑loss or Device Fault) | Normally‑closed Contact (Open during normal operation) | AC250V 5A;DC30V 5A |
| X2.3‑X2.4(Fault Signal) | Normally‑open Contact | AC250V 5A;DC30V 5A |
| X2.5‑X2.6(Programmable Output) | Normally‑open Contact | AC250V 5A;DC30V 5A |
| X2.7‑X2.8(Programmable Output) | Normally‑open Contact | AC250V 5A;DC30V 5A |
| X2.9‑X2.10(Programmable Output) | Normally‑open Contact | AC250V 5A;DC30V 5A |
| X2.11‑X2.12(Start‑up 1) | Normally‑open Contact | AC250V 8A;DC30V 8A |
| X2.13‑X2.14(Start‑up 2) | Normally‑open Contact | AC250V 8A;DC30V 8A |
4.4 4-20mA output
| Load Resistance | <800ω |
| Output Ripple | <20mV |
| Response Time | <100ms |
4.5 Communication
| Communication Interface | 2‑channel optional, RS485 |
| Communication Protocol | MODBUS/PROFIBUS |
| Baud Rate | 2400‑19600 configurable |
| Address | 1‑255 |
4.6 Device Power Supply
Scope of work: AC80V-250V or DC90V-250V
Power consumption ≤ 5W during normal operation
Protection action ≤ 8W
Auxiliary power supply allows interruption time ≤ 200mS
4.7 Environmental Conditions
Allowable temperature
Working at -15 ℃ to+55 ℃
Storage -25 ℃~+70 ℃
Allow humidity
Relative humidity ≤ 95%, no condensation
Altitude ≤ 3000m
4.8 Mechanical Properties
Vibration: able to withstand the harsh level I vibration durability test specified by IEC standards
Impact: able to withstand the impact durability test with severity level I specified by IEC standards
Collision: able to withstand the harsh level I collision durability test specified by IEC standards
4.9 Electromagnetic compatibility test
| Electrostatic Discharge Immunity | ±15KV |
| Radiated Radio‑Frequency Electromagnetic Field Immunity | 80MHz‑1GHz 10V/m |
| Electrical Fast Transient Burst Immunity | ±4KV/2.5KHz |
| Surge Immunity | Line‑to‑Ground ±4KV Line‑to‑Line ±2KV |
| Conducted Radio‑Frequency Immunity | 150KHz‑80MHz Level: 10V |
| Power‑frequency Magnetic Field Immunity | Continuous magnetic field 100A/m Short‑time magnetic field 300A/m Class V |
| Pulsed Magnetic Field Immunity | 300A/m |
| Damped Oscillatory Magnetic Field Immunity | 30A/m Class VI |
| Voltage Dips, Short Interruptions and Voltage Variations Immunity | Dips & short interruptions 0%UT; Voltage variation 40%UT |
| Oscillatory Wave Immunity | 100KHz 1MHz Common‑mode 2.5KV Differential‑mode 1KV |
| Power‑frequency Immunity | Class A Differential‑mode 150V Common‑mode 300V |
| Conducted Emission Limits | 150KHz‑30MHz |
| Radiated Emission Limits | 30MHz‑1GHz <57μV/m |
| Harmonic Current Emission Limits | Class A 15th harmonic |
| Voltage Fluctuations and Flicker | Complies with IEC61000‑3‑3 |
4.10 Electrical Testing
Insulation resistance 100M Ω/500V
Dielectric strength test 2KV (r.m.s), 50Hz, 1min
Impulse voltage test ± 5KV; 1.2/50 µ S