TZY-XH-PC/TZ/TR arc suppression coil system
Add time:2022-02-21
Page views:83
Dial +86-312-3156390 / 3155390For power systems with different voltage levels, the grounding method for neutral points is different. According to China's national conditions, the small current grounding operation mode is mainly used in the 6-66KV distribution system in China. In order to effectively prevent system arc grounding, eliminate grounding faults, and improve power supply quality, according to the new regulations of the national overvoltage protection design standards, arc suppression coil devices should be installed when the grid capacitor current exceeds 10A. One advantage of this grounding method is that the grounding current of the power system with the neutral point grounded through the arc suppression coil is small, and it causes less interference to nearby communication.
Previously, China's power grid commonly used manual turn controlled arc suppression coils. Due to the inability to monitor the capacitance current of the power grid in real time, its main defects were manifested in the following two aspects:
(1) Adjustment is inconvenient and requires the device to be shut down before it can be adjusted.
(2) It is difficult to make accurate judgments on the operating status of the system, making it difficult to ensure that the detuning and neutral point displacement voltage meet the requirements.
The TZYXH-TZ series adjustable turn arc suppression coil device developed and produced by our company adopts a standard industrial grade computer system, bus structure, multi-layer circuit board design, full-color large screen LCD screen, and full Chinese character display. It has the characteristics of stable and reliable operation, intuitive display, strong anti-interference ability, and the system also has parameter setting and information query functions. This system overcomes the limitation of small adjustment range of previous arc suppression coil devices and can be adjusted.
This product is widely used in the power supply industry, power plants, metallurgy, mining, coal, paper, petrochemical and other large industrial and mining enterprises' transformer and distribution stations. It is suitable for voltage levels of 6~110KV and is an ideal replacement product for old-fashioned arc suppression coils. It is also a supporting product for grounding compensation and line selection devices in new substations.
(1) The controller adopts an industrial grade computer platform, dual CPU architecture, multi-layer circuit board processing, and runs stably and reliably.
(2) Adopting full-color LCD display in Chinese, parameter display, setting and query are convenient and intuitive.
(3) Accurate adjustment, fast speed, and wide adjustment range.
(4) Equipped with RS485 communication interface, it can achieve communication with the upper computer and achieve long-distance signal transmission.
(5) It can achieve sound and light control alarm function for single-phase grounding faults.
(1) Voltage level: 6KV~110KV
(2) Measurement error of capacitance current: less than 2%
(3) Adjustment time: less than 20ms
(4) Grounding residual current: less than 5A
(5) Controller power supply: AC 220V, rated frequency: 50Hz
(6) Controller applicable environment
Temperature: -10 ℃~+45 ℃
Humidity: less than 95%
(7) Communication interface: RS485


86-312-3156390