1. Meet all on-site testing requirements. This instrument has standard six phase voltage and six phase current output, which can be used to test various traditional relays and protection devices, as well as various modern microcomputer protections, especially for transformer differential power protection and backup automatic switching devices, making testing more convenient.
2. All technical indicators fully meet the standards of DL/T624-1997 "Technical Conditions for Microcomputer based Test Devices for Relay Protection" issued by the Ministry of Electric Power.
3. Classic Windows XP operating interface, user-friendly human-machine interface, easy and fast operation; A high-performance embedded industrial control computer and an 8.4-inch TFT true color display screen with a resolution of 800 × 600 can provide rich and intuitive information, including the current working status of the device and various help information.
4. The Windows XP system comes with a built-in recovery function to prevent system crashes caused by illegal shutdowns or misoperations.
5. Equipped with a thin industrial keyboard and optical mouse, various operations can be completed through the keyboard or mouse just like operating a regular PC.
6. The main control board adopts a DSP+FPGA structure and a 16 bit DAC output, which can generate a high-density sine wave of 2000 points per week for the base wave, greatly improving the quality of the waveform and enhancing the accuracy of the tester.
7. The power amplifier adopts high fidelity linear power amplifier, which has both low current accuracy and high current stability.
8. It uses a USB interface to communicate directly with the PC without any adapter cables, making it convenient to use.
9. Can be connected to a laptop (optional) for operation. Laptops and industrial computers use the same software, so there is no need to relearn the operating methods.
10. Equipped with GPS synchronization test function. The device can be equipped with a built-in GPS synchronization card (optional) and connected to a PC through an RS232 port, enabling two testers to perform synchronous testing in different locations.
11. Equipped with independent DC auxiliary voltage source output, with output voltages of 110V (1A) and 220V (0.6A) respectively. To be used for relays or protective devices that require DC working power supply.
12. It has software self calibration function, which avoids the need to open the chassis and adjust the potentiometer to calibrate accuracy, greatly improving the stability of accuracy.
1.1 AC Current Source (6×30A)
| Single‑phase Current Output (RMS) | 0--30A/phase, Accuracy: 0.2% ±5mA |
| Six‑phase Parallel Output (RMS) | 0--180A for six‑phase same‑phase parallel output |
| Long‑term Allowable Operating Value of Phase Current (RMS) | 10A |
| Maximum Output Power per Phase | 300VA |
| Maximum Output Power for Six‑phase Parallel Current | 1000VA |
| Allowable Operating Time for Maximum Six‑parallel Current Output | 10s |
| Frequency Range | 0--1000Hz, Accuracy 0.01Hz |
| Harmonic Order | 2--20 |
| Phase Angle | 0--360°, Accuracy 0.1° |
2. DC Current Source
| DC Current Output | 0--±10A/phase, Accuracy: 0.2% ±5mA |
3. AC Voltage Source
| Single‑phase Voltage Output (RMS) | 0--125V/phase, Accuracy: 0.2% ±5mV |
| Line Voltage Output (RMS) | 0--250V |
| Phase‑voltage / Line‑voltage Output Power | 75VA / 100VA |
| Frequency Range | 0--1000Hz, Accuracy: 0.001Hz |
| Harmonic Order | 2--20 |
| Phase Angle | 0--360°, Accuracy: 0.1° |
4. DC Voltage Source
| Single‑phase Voltage Output Amplitude | 0--±150V, Accuracy: 0.2% ±5mV |
| Line Voltage Output Amplitude | 0--±300V |
| Phase‑voltage / Line‑voltage Output Power | 90VA / 180VA |
5. Digital I/O Terminals
| Digital Input Terminals | 8 pairs |
| Vacant Contact | 1--20mA, 24V internal active output of device |
| Potential Flip | Passive contact: low‑resistance short‑circuit signal Active contact: 0‑250V DC |
| Digital Output Terminals | 4 pairs, vacant contact, Interrupt capacity: 110V/2A, 220V/1A |
6. Others
| Time Range | 1ms--9999s, Measurement accuracy: 1ms |
| Single‑unit Dimensions & Weight | Dimensions: 410 × 190 × 420mm³, approx. 18Kg |
| Power Supply | AC220V±10%, 50Hz, 10A |