86-312-3156390
  • Switch testing products
    Your location:Home > Product > 高试仪器事业部 > Switch testing products

    Become a respected enterprise

    TZY-SC8001 High Voltage Switch Action Characteristics Tester

    High voltage circuit breakers play a dual role in control and protection in the power system, and their performance directly affects the operation of the power system. Mechanical characteristic parameters are one of the important parameters for judging the performance of circuit breakers.
    Add time:2022-02-15
    Page views:79
    Dial +86-312-3156390 / 3155390
    Product Overview

    With the development of society, people have increasingly high requirements for the reliability of electricity use. High voltage circuit breakers play a dual role in control and protection in the power system, and their performance directly affects the operation of the power system. Mechanical characteristic parameters are one of the important parameters for judging the performance of circuit breakers. The TZY-SC8001 high-voltage switch action characteristic tester, also known as the high-voltage switch mechanical characteristic tester, is designed based on the "High Voltage AC Circuit Breaker" GB1984-2003 as the blueprint, and refers to the Chinese power industry standard "General Technical Conditions for High Voltage Testing Equipment" Part 3, DL/T846.3-2004 as the design basis. It provides convenience for dynamic analysis of various types of circuit breakers and can accurately measure the mechanical dynamic characteristic parameters of low oil, high oil, vacuum, sulfur hexafluoride and other high-voltage circuit breakers of various voltage levels. High voltage circuit breakers play a dual role in control and protection in the power system, and their performance directly affects the operation of the power system. Mechanical characteristic parameters are one of the important parameters for judging the performance of circuit breakers.

    Features

    1. Time

    This machine can measure the inherent opening and closing time, in-phase synchronization time, face-to-face synchronization time, metal short time and no current time during the closing opening, opening closing, and opening closing opening processes of 12 metal fracture surfaces, as well as the closing bounce time. Some models can also measure the pre switching time of the closing resistance.

    2. Speed and Travel

    This machine can record and measure the closing bounce time, bounce frequency, bounce process, and bounce waveform of each fracture.

    3. Speed and Travel

    This machine can record and calculate the speed of rigid opening and closing, average speed, total travel, opening distance, over travel, time, and travel characteristic curve.

    4. Current and voltage

    This machine can record the opening/closing current values and current waveform diagrams of the opening/closing coils, provide DC5-270V/10A digital adjustable circuit breaker action power supply, automatically complete the low voltage action test of the circuit breaker, and measure the action voltage value of the circuit breaker.

    Specifications

    1. Usage environment

    Input power supply: 220V ± 10%, 50Hz ± 10%

    Atmospheric pressure: 86-106 kPa

    Temperature: -10~40 ℃

    Humidity: ≤ 80% RH

    2. Performance

    Insulation resistance:>2M Ω

    Dielectric strength: The power supply can withstand the 1.5KV power frequency voltage of the casing for 1 minute without flashover or arcing

    3. Basic parameters

    3.1 Time

    When the range is selected as 250-4000ms, the resolution is 0.1ms and the error is 0.1ms ± 1 word; When the range is 10000-20000ms, the resolution is 1ms and the error is 1ms ± 1 word.

    3.2 Speed

    The measuring range is 20.00m/s, the resolution is 0.001m/s, and the error is ± 0.01m/s ± 1 word.

    3.3 Current

    The measuring range is 10A, the resolution is 0.01A, and the error is 1% ± 0.1A.

    3.4 Output power supply

    DC5-270V digital adjustable 10A (instantaneous operation).

    3.5 Journey

    Switch typeRange (mm)Resolution (mm)Error
    Vacuum circuit breaker500.11%±1个字
    SF6 circuit breaker300
    Low oil circuit breaker1000


    Table 1

    3.6 Dimensions: Host 360 * 390 * 170 (mm)

    Wire box 425 * 335 * 210 (mm)

    Weight: Main unit 5.5KG, wire box 8KG

    Test line length: Standard 8-meter length can be customized


    • Registered address: Room 302, Building 6, Baoding Zhongguancun Digital Economy Industrial Park, 777 Lixing Street, Gaokai District, Baoding City, Hebei Province

    • Mobile:+86-152-000-51135 (working hours)
                  +86-137-2296-5163 (off hours)
                  +86-136-6330-3815
      Online:+86-312-3156390/3155390

    • Marketing internal email: tzydq_yxb@163.com
      Technical Email: tzydq_jsb@163.com

    Copyright © Hebei Taizhongyan Electrical Equipment Technology Co., Ltd https://www.tzydq.com/ All Rights Reserved  Record number:冀ICP备13014722号-1    Friendship links: Optoelectronic Materials Division   Distribution Monitoring Division  
    HomeTelProduct